Comeco logo

Advantages

  • High resistance to electromagnetic disturbances
  • Up to 10 selectable ranges for Pt100 sensors
  • Up to 10 selectable thermocouples
  • In-head and DIN-rail versions
  • IP65 box and Ex housing available

Description

COMECO’s temperature transmitter TRA is a compromising solution between the analog transmitters with fixed range and the programmable transmitters. TRA allows on-site selection of input range and sensor type (for thermocouples) as well as transmitter reaction to sensor failure by the means of a group of soldering bridges (jumpers). The exact range is adjustable by ZERO and SPAN potentiometers. TRA is available in case for mounting inside sensor protection head, in watertight box with high protection class, in case for mounting on a DIN rail, and in case prepared for mounting in Ex housings. Thanks to its flexibility, excellent resistance against electromagnetic disturbances, and low price, TRA is easy to use and very widely applicable.

Additional information

Корпус

18x90x58 mm, 80x80x60 mm, ø44×19 mm

Монтаж

DIN rail, In box IP65, In head, In Ex housing

Аналогов вход

RTD Pt100 – 1.385, Thermocouple (TC) E, Thermocouple (TC) J, Thermocouple (TC) K, Thermocouple (TC) L, Thermocouple (TC) L – GOST, Thermocouple (TC) N, Thermocouple (TC) R, Thermocouple (TC) S, Thermocouple (TC) T, Thermocouple (TC) U

Аналогов изход

20…4 mA, 4…20 mA

Захранване

8…32 VDC

TRA transmitter

Current / Voltage / ResistanceTemperature

Technical Specifications
Input
Pt100 (w=1.385); 3-wire 0…50/ 100/ 150/ 200/ 300/ 400/ 500 °C; -50…50/ 100 °C (1); 0…250 °C (1)
Thermocouple “E”0…300/ 400/ 500/ 600 °C
Thermocouple “J”0…400/ 500/ 600/ 800 °C
Thermocouple “K”0…600/ 800/ 1000/ 1200 °C
Thermocouple “L” (2)0…700 °C
Thermocouple “L – GOST” (2)0…600 °C
Thermocouple “N”0…800/ 1000/ 1200 °C
Thermocouple “R” (3)0…1200/ 1400/ 1600 °C
Thermocouple “S” (3)0…1200/ 1400/ 1600 °C
Thermocouple “T”0…100/ 200/ 300 °C
Thermocouple “U” (3)0…100/ 200/ 300/ 400 °C
Range selectionwith jumpers
Thermocouple selectionwith jumpers
ZERO adjustment± 50 °C ± 10%
SPAN adjustment ± 10%
Output
Signal type 4…20 mA
RTD linearly proportional to
temperature
T/C linearly proportional to input voltage
Current limits Low: 23 mA
Reaction at RTD failure:Low or High
– for variant ‘1’depends on terminal
– for variant ‘2’ selectable
Reaction at T/C failureHigh
Accuracy
Measurement error 0.3% from span
Non-linearity0.3% from span
Self-heating error0,02%/mA at 24 V
Temperature drift0.02% from span for 1 °C
Cold junction compensationautomatic hardware, ± 1 °C
Power supply
Supply voltage8…32 VDC
Admissible variations1 Vp-p at 50 Hz
Maximum line load:for variant ‘1’620 Ω (800 Ω for T/C) at 24V/20mA
for variant ‘2’ 700 Ω (800 Ω for T/C) at 24V/20mA
Operating conditions
Ambient temperature: – for variant ‘1’ -20…70 °C
– for variant ‘2’ -40…85 °C
Ambient humidity0…95 %RH, non-condensing
Design and materials
Case materialplastic
Wiringscrew terminals
Mounting in head (4,5,6)on rail (1)in box (5)
Dimensions [mm] ø44×1918x90x5880x80x60
Weight 30 g90 g170 g
Protection classIP20IP20IP65

(1) Available only for variant ‘1’.

(2) Ask for availability!

(3) Available only when in case for DIN-rail mounting (G12 = “C”)!

(4) Head type “B” or any other with 33 mm distance between centers of the female threaded openings

(5) May be mounted on rail by a special snap-on accessory, which is ordered separately (see ‘Accessories’).

(6) May be mounted in different, separately ordered Ex housings for field applications (see ‘Accessorie