Comeco logo

Advantages

  • Input / output / supply triple isolation
  • Accepts mA, mV, V, or & linear signals
  • Positive and negative mA or V output
  • Built-in digital filter
  • Direct and reverse conversion
  • Full digital technology – no analog adjustments
  • DIN-rail mounting
  • 11-pin box for DIN-rail mounting

Description

COMECO’s signal isolator TRIM is an active triple-isolated transmitter with separate isolated power supply with 1000 VAC isolation level. The input part is internally powered and generates 24 VDC excitation voltage for external devices connected to TRIM input (current loops, transmitters, etc.). The input may accept various mA, mV, V (unipolar and bipolar) as well as resistive linear signals. The output part is internally energized and generates standard or custom specified linear current or voltage (positive or negative) signals. Thanks to the use of high sophisticated electronics for its manufacturing, the TRIM isolator offers some special features that can be activated by the user via internal programming jumpers:

  • direct or reversed conversion;
  • upscale or downscale output status at input failure;
  • custom specified non-linear conversions.

TRIM is available in a case for mounting on a 35 mm DIN rail according to EN50022 and in a convenient 11-pin box for socket mounting.

Additional information

Монтаж

DIN rail, In box IP65

Корпус

23x90x58 mm, 35x78x91 mm

Захранване

12…24 V, isolated

Аналогов вход

-1…1 V DC linear voltage, -10…10 V DC linear voltage, 0…1 V DC linear voltage, 0…10 V DC linear voltage, 0…100 mV DC linear voltage, 0…2 V DC linear voltage, 0…20mA DC linear current, 0…5 V DC linear voltage, 0…50 mV DC linear voltage, 0…5mA DC linear current, 4…20mA DC linear current, Resistive

Аналогов изход

0…20 mA, 0…5 mA, 1…5 mA, 2…10 mA, 4…20 mA, Other

TRIM transmitter

Current / Voltage / ResistanceTemperature

Technical Specifications
Input
Linear current 0…5 mA, 0(4)…20 mA
Linear voltage0…50 mV, 0…100 mV, 0…1 V, -1…1 V,0…2 V, 0…5 V, 0…10 V, -10…10 V
Linear resistive 0…1 kΩ
Custom linear (option) min. -10…max. 10 V (1), 0…max. 100 mA(1),
0…100 Ω…100 kΩ (1)
Current-input impedancemax. 10 Ω
Voltage-input impedancemin. 1 GΩ (1 MΩ for range span > 1.5 V)
Input isolation> 1000 VAC for 1 min
Output
Linear current 0(1)…5 mA, 2…10 mA, 0(4)…20 mA
Liner voltage 0…1 V, 0…2 V, 0(1)…5 V, 0(2)…10 V
Custom linear (option) on request (1)
Current-output loadmax. 620 Ω
Voltage-output loadmin. 1 kΩ (2)
Direct or reverse conversionselectable
Output signal at input failureupscale or downscale, selectable
Output isolation> 1000 VAC for 1 min
Excitation voltage24 VDC, max. 30 mA
Accuracy
Measurement error0.1% from span
Temperature drift 0.01% from span for 1 °C
Power supply influence negligible
Power supply
Supply voltage12…24 V
Consumptionmax. 100 mA
Isolation> 1000 VAC for1 min
Operating conditions
Ambient temperature -20…70 °C
Ambient humidity0…95 %RH, non-condensing
Design and materialsR1R2
Dimensions [mm]23x90x5835x78x91
Mounting on rail in socket or on rail
Maximum weight [g]80180
Protection classIP20IP20
Case materialplastic plastic
Wiring screw terminalssocket UNDECAL (3)

(1) On request. Specify range additionally!

(2) Minimum 50 kΩ for negative output voltage ranges!

(3) Ordered separately (see ‘Accessories’)