Comeco logo

Advantages

  • Low-cost network transmitter – up to 32 devices
  • Universal programmable input
  • User-selectable 4 RTD types and 6 thermocouples
  • Accepts linear current and voltage signals
  • Built-in programmable digital filter
  • Convenient programming through RS485
  • Supported protocols: ASCII, ASCII for “PolyMonitor”, MODBUS
  • Input / output / supply isolation

Description

TRIS is a programmable transmitter that converts signals from various sensors into a digital code transmitted over an isolated RS485 interface. Compatible with up to 32 devices in a network, it supports universal input for RTD, thermocouple and linear signals, providing precise monitoring and data recording in industrial applications. The transmitter allows the user to:

  • select the type of sensor and input signal (4 RTDs, 6 thermocouples and 4 linear signals);
  • select and set the input range;
  • enter zero correction and calibrate the output;
  • select the unit of measurement and the position of the decimal point;
  • set digital filters.

 

TRIS Applications:

TRIS is widely used in industrial monitoring and control systems, where data collection from multiple points is required via a single communication line. Thanks to its universal input and networking capabilities, the transmitter is suitable for:​

  • Automation of production processes: Collection and transmission of data from various sensors for production optimization.​
  • Energy: Monitoring of temperature and other parameters in energy installations.​
  • Chemical industry: Monitoring of critical processes by integrating multiple sensors into a network.​
  • Food and beverage industry: Control of parameters such as temperature and humidity in production and storage facilities.​
  • Environment: Collection of data from sensors for monitoring environmental indicators.

The flexibility and reliability of TRIS make it a valuable tool for building effective and scalable monitoring and control systems in various industrial sectors.

Additional information

Протокол

ASCII, ASCII PolyMonitor, Modbus

Монтаж

DIN rail

Корпус

35x110x58 mm

Интерфейс

RS485

Аналогов вход

0…10 V DC linear voltage, 0…100 mV DC linear voltage, 0…20mA DC linear current, 4…20mA DC linear current, Custom linear signal, RTD Pt100 – 1.385, RTD Pt1000 – 1.385, RTD PTC 1k, RTD PTC 2k, Thermocouple (TC) B, Thermocouple (TC) J, Thermocouple (TC) K, Thermocouple (TC) R, Thermocouple (TC) S, Thermocouple (TC) T

TRIS – Intelligent network transmitter with RS485 interface and universal input

Current / Voltage / ResistanceTemperature

Technical Specifications
Input (programmable)
Pt100 (w=1.385); 3-wire (DIN IEC 60751)min. -100…max. 850 °C
Pt1000 (w=1.385); 3-wire (DIN IEC 60751)min. -100…max. 600 °C
PTC (1k at 25 °C); 3-wire (KY and KTY based)min. -50…max. 150 °C
PTC (2k at 25 °C); 3-wire (KY and KTY based)min. -50…max. 150 °C
RTD minimum range width50 °C
Thermocouple “T” (DIN IEC 60584)min. -40…max. 400 °C
Thermocouple “J” (DIN IEC 60584)min. -20…max. 1000 °C
Thermocouple “K” (DIN IEC 60584)min. -20…max. 1300 °C
Thermocouple “S” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “R” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “B” (DIN IEC 60584)min. 200…max. 1800 °C
T/C minimum range width100 °C
Linear current 0(4)…20 mA
Linear voltage0…100 mV or 0…10 V
Custom linear (option) on request (1)
Offset adjustment within range limits
Digital low-pass filterprogrammable
Digital peak filterprogrammable
Isolation> 1000 VAC for 1 min
Output / Interface
Interface typeRS485
Functionconfiguration and networking
Network devices up to 32
Format8 (data) + 1 (stop), even parity
Baud rate1200 / 2400 / 4800 / 9600 bps
Isolation2500 VAC for 1 min
Software (2)
Configuration softwareUniConf”, free
Monitoring and data acquisition“PolyMonitor
Accuracy
Measurement error0.3% from span
Non-linearitywithin measurement error
Temperature drift 0.01% from span for 1 °C
Cold junction compensation automatic software, ± 0.5 °C
Power supply
Supply voltage12…24 V
Consumption max. 100 mA
Indication
‘ON’ LED for power supply ON
‘SEL’ LEDfor active communication
Operating conditions
Ambient temperature-20…70 °C
Ambient humidity 0…95 %RH, non-condensing
Design and materials
Case material plastic
Wiring plug-in terminals
Mountingon 35 mm DIN rail
Dimensions35x110x58 mm
Weight90 g
Protection classIP20

(1) Instead of linear current