Comeco logo

Advantages

  • 6 DIN cases – up to 1/32 DIN
  • Indicator with 4-digit bright LED display
  • Universal linear input
  • Up to 2 alarm relays available with pulsed output
  • Fully programmable parameters

Description

TI08 is a universal programmable process indicator designed for precise measurement and control of process parameters. Equipped with a bright 4-digit display, this model is particularly suitable for monitoring and controlling alarm limits in the range from -1999 to 9999 with a resolution of up to 6000 points. TI08 supports a variety of linear voltage and current signals at the input and can be equipped with up to 2 programmable relay outputs, providing on/off control or pulse alarm. Available in 6 DIN housings. Thanks to the excellent price-performance ratio. The correspondence of the input and display, the decimal point location, the correction of the reading and many other parameters are fully programmable.

TI08 Application:

Thanks to its excellent price-performance ratio, TI08 finds wide application in industrial automation and control systems. Thanks to its high accuracy and universal inputs for linear current and voltage signals, it is suitable for:

• Production lines – monitoring and control of critical parameters
• Food and beverage industry – monitoring of technological processes
• Chemical and pharmaceutical industry – measurement and control of parameters in production plants
• Refrigeration and air conditioning installations – precise control of temperatures and other technological values

Additional information

Корпус

48×24 mm, 48×48 mm, 48×96 mm, 72×36 mm, 96×48 mm, 96×96 mm

Захранване

115 VAC, 230 VAC, 9(12) VAC with external transformer, 90…250 V

Релеен изход

Relay NO

Повишена лицева защита

IP65

Аналогов вход

0…10 V DC linear voltage, 0…20mA DC linear current, 0…5 V DC linear voltage, 4…20mA DC linear current, Custom linear signal, Two-wire external transmitter

Programmable Process Indicator TI08 with 4-digit LED display and relay outputs

Current / Voltage / ResistanceTemperature

From: 51.39 

    Select up to 2 outputs

    Output 1
    Output 2
Technical Specifications
Input (programmable)
Linear voltage 0…10 V-1999…9999, programmable
Linear voltage 0…5 V (1)-1999…9999, programmable
Linear current 0(4)…20 mA-1999…9999, programmable
Custom linear (option)-1999…9999, programmable
Two-wire external transmitter4…20 mA (2)
Decimal point selectionprogrammable
Outputs (up to 2 relay outputs (3))
Relay electromechanical 5A/250V w/ NO/NC (4) contact
Solid state relay (SSR) (7) 1A/250VAC (5)
MOS gate (7) 0,1A/60V, optically isolated
Output for external SSR 5…24 V, 30 mA
Control algorithmON/OFF, pulse mode
Alarmsprogrammable
Accuracy
Measurement error0,3% from span
Temperature drift0,02% from span for 1 °C
Operating conditions
Ambient temperature-10…65 °C
Ambient humidity0…85 %RH
Power supply
Mains supply voltage (1)230 VAC or 115 VAC
SMPS voltage (1)90…250 V
Isolated low voltage12…24 V or 24 VAC
Non-isolated low voltage12…24 V
External mains transformer (6)9(12) VAC
Consumptionmax. 1,5 VA
Indication and controls
Digital display4 LED indicators
LEDs2 LEDs for output state
Keyboard2 мембранни бутона; заключваща се

 

Design and materialsBH / VSLM
Front dimensions [mm]96×9696×4848×4872×3648×24
Mountingpanelpanelpanelpanelpanel
Panel cutout [mm]90×9090×4245×4571×2946×22
Mounting depth [mm]98981005642
Display digit height [mm]2014 / 910149
Maximum weight [g]35025020015030
Protection, front/terminalsIP54/20IP54/20IP54/20IP54/20IP54/20
Increased front IP (option)IP65IP65IP65
Case materialplasticplasticplasticplasticplastic
Wiring (terminals)plug-inplug-inscrewscrewscrew

(1) Not available for case ‘M’
(2) Provides loop supply voltage – 24 VDC (only w/ isolated power supply)
(3) Only one for case ‘M’
(4) For case ‘S’ 2nd relay is NO; for case ‘L’ both relays are NO; for case ‘M’ relay is NO
(5) 0.2A/250VAC for cases ‘L’ and ‘M’
(6) Available only for case ‘M’. Transformer is ordered separately.