Comeco logo

Advantages

  • Indicator with 8 inputs, 8 outputs, and 16 alarms
  • Indicator with 2 displays – for measured value and for channel number
  • Programmable ranges and alarms
  • Self-testing and system-failure alarm
  • RS485 serial interface available

Description

The TC800 indicator is designed for multi-point control of technological variables. With its compact design, 8 inputs and outputs, TC800 successfully performs all the tasks of indicating, monitoring, and signaling the level of several channels. With the proper programming, any of the channels may be turned into a 2-or 3-state ON/OFF controller and even into a multistage controller. Motorized actuators may be controlled by using 2 relay outputs. The device input accepts thermoresistances, thermocouples, or standard current and voltage signals. Additional discrete inputs are available for remote channel switching and tampering protection. TC800 performs digital compensation for RTD sensor line resistance as well as thermocouple cold-junction compensation, and constantly monitors sensor and sensor-lead state. A rich set of parameters allows programming every aspect of controller operation and an RS485 serial interface allows network operation or connection to operator station.

Additional information

Захранване

115 VAC, 230 VAC, 90…250 V

Релеен изход

Relay NO

Аналогов вход

0…1 V DC linear voltage, 0…10 V DC linear voltage, 0…2 V DC linear voltage, 0…20mA DC linear current, 0…5 V DC linear voltage, 4…20mA DC linear current, Other, RTD Cu100 – 1.426, RTD Cu100 – 1.428, RTD Cu50 – 1.426, RTD Cu50 – 1.428, RTD Pt100 – 1.385, RTD Pt100 – 1.391, RTD Pt1000 – 1.385, RTD Pt50 – 1.385, RTD Pt50 – 1.391, RTD Pt500, Thermocouple (TC) B, Thermocouple (TC) E, Thermocouple (TC) J, Thermocouple (TC) K, Thermocouple (TC) L, Thermocouple (TC) L – GOST, Thermocouple (TC) R, Thermocouple (TC) S, Thermocouple (TC) T, Thermocouple (TC) U

Цифров вход

Contact, None, NPN, PNP, TTL

Интерфейс

None, RS485

Протокол

ASCII, ASCII PolyMonitor, Binary, Binary PM

Аларми

None, System

Повишена лицева защита

IP65

Корпус

96x96x107 mm

Монтаж

TC800 indicator

Current / Voltage / ResistanceHumidityTemperature

Technical Specifications
Analog inputs (2…8 inputs)
Pt10…1000 (w=1.385, 1.391)-100(-200)…200(850) °C (1)
Cu50, Cu100 (w=1.426, 1.428)-50(0)…200 °C (1)
Other RTD (1)min. -200…max. 850 °C
Thermocouple “J”0…800 °C
Thermocouple “K”0…1200 °C
Thermocouple “S”0…1600 °C
Thermocouple “R” 0…1600 °C
Thermocouple “B” 200…1800 °C
Thermocouple “L”0…1200 °C
Thermocouple “L – GOST”0…600 °C
Thermocouple “E” 0…1000 °C
Thermocouple “T”0…400 °C
Thermocouple “U”0…600 °C
Other thermocouple (1)min. 0…max. 2400 °C
Linear voltage 0…1/ 2/ 5/ 10 V-999…9999, programmable
Linear current 0(4)…20 mA-999…9999, programmable
Custom linear voltage; max. 40 V (1)min. -999…max. 9999, programmable
Custom linear current; max. 50 mA (1)min. -999…max. 9999, programmable
Discrete inputs (up to 2 inputs)
Input signal typecontact, TTL, NPN, or PNP
Input 1 functionremote channel selection
Input 2 functionext. programmed parameter protection
Outputs (up to 9 relay outputs) (2)
Relay electromechanical5A/250V w/ NO contact (3)
Solid state relay (SSR) (5) 1A/250VAC
MOS gate (5) 0.1A/60V, optically isolated
Output for external SSR5…24 V, 30 mA
Alarmsup to 16, programmable
System-failure alarmactivates SPDT EMR output No 9
Serial interface RS485, isolated (4)
Accuracy
Measurement error 0.4% from span
Temperature drift0.005% from span for 1 °C
Cold junction compensation± 1 °C, automatic software
RTD line compensation software
Power supply
Mains supply voltage230 VAC or 115 VAC
SMPS voltage 90…250 V
Isolated low voltage12…24 V or 24 VAC
Consumption max. 4 VA
Indication and controls
Channel-number display2 green LED indicators, 14 mm
Measured-value display4 red LED indicators, 14 mm
LEDs 8 LEDs for output state
and 16 LEDs for alarm state
Keyboard 8 membrane keys
Operating conditions
Ambient temperature -10…65 °C
Ambient humidity0…85 %RH
Design and materials
Case materialplastic
Mountingin 90×90 mm panel cut-out
Wiringplug-in terminals
Dimensions 96×96(front)x107 mm
Mounting depth 98 mm
Weight макс. 650 g
Protection, front/terminalsIP54 / IP20
Increased front IP (option)IP65

(1) Custom; specify range within the limits stated.

(2) Relay No 9 is for system-failure alarm only (G10)!

(3) NO/NC for relay No 1

(4) With ASCII protocol, the outputs may be controlled only through the interface, and with binary protocol – only through the hardware!

(5) Ask for availability!