Comeco logo

Advantages

  • Up to 4 electrodes (3 plus reference)
  • Fixed or changeable electrodes
  • Applicable to conductive liquids
  • Compatible with LC level controllers/indicators
  • Electrode coating available
  • Local controller available
  • ATEX certified Ex version available

Description

The LCSA6 level probe is intended for multi-point control of conductive liquids in combination with conductivity level controllers/indicators, such as the controller series LC produced by COMECO. Up to 4 replaceable rod-type electrodes (4 operating or 3 operating and 1 reference) can be attached to the probe header. LCSA6 can be mounted on the top of various vessels: metal or nonmetal, open-surface, closed, or pressurized up to 16 bar. The (insulated) stainless steel wetted parts allow usage in the food, pharmaceutical, and chemical industries, and the available Ex ‘d’ approved enclosure provides a high grade of protection. Thanks to its compact design, the LCSA6 probe is very useful in multi-level control applications.

Additional information

Вид сензор за ниво

Conductive multipoint

Присъединяванe

Flange, G1½", G2", NPT 1½", NPT 2", Other

LCSA6 multi-point conductive level probe

Level

Technical Specifications
ModelLCSA6
Specifications
Electrodes1, 2, 3, or 4 operating electrodes (1) + reference electrode (2)
Probe length60…3000 mm for each electrode
Process connection1½”, 2″, or flange
Rod insulationnone or PTFE tube
Wiringin-head screw w/ nuts; through cable gland
Mountingtop
Wetted partsstainless steel, PTFE
HousingIP65 ABS box 80x80x60 mmIP65 aluminum protection headEx ‘d’ IP66 stainless steel protection head
Operating temperature-20…90 °C -20…200 °C -20…200 °C
Operating pressureup to 16 bar
Rod separatorPTFE disc w/ 5 mm thickness (3)
ATEX approvalII 2G Ex d IIC T6 -20°C≤Ta≤+60°C, II 2D Ex tDA21 IP65 T80°C

 

ModelLCSA6S
Specifications
Descriptionsocket for changeable electrodes LCSAR (4)
Electrodesfor 1, 2, 3, or 4 operating electrodes (1) + reference electrode (2)
Probe/socket insulationPTFE
Process connection1½”, 2″, or flange
Rod connectionM6 (female)
Wiringin-head screw w/ nuts; through cable gland
Mountingtop
Wetted partsstainless steel, PTFE
HousingIP65 ABS box 80x80x60 mmIP65 aluminum protection headEx ‘d’ IP66 stainless steel protection head
Operating temperature-20…90 °C -20…200 °C -20…200 °C
Operating pressureup to 16 bar
ATEX approvalII 2G Ex d IIC T6 -20°C≤Ta≤+60°C, II 2D Ex tDA21 IP65 T80°C

(1) Electrically isolated from the metal housing!
(2) Non obligatory electrode, which is electrically connected to the metal housing!
(3) It is obligatory, if two of the rods are longer than 500 mm; can also be ordered separately.

(4) See LCSA datasheets and order separately!