Comeco logo

Advantages

  • DIN-rail mounting
  • 11-pin box for DIN-rail mounting
  • 3-digit bright LED display
  • Universal input for 4 RTDs, 6 T/Cs, and 4 linear types
  • RS485 serial interface available

Description

RT28U-R is a modification of RT28U for rail mounting. It is equipped with a 3-digit LED display, a universal input for Pt100, Pt1000, PTC, 6 thermocouple types as well as for linear current, voltage, and resistive signals from external transmitters and can have up to 2 programmable relay control/alarm outputs. The device has a built-in circuit for self-testing and self-calibration, manual measurement offset setting, and automatic software compensation of line resistance and cold junction temperature. The display-to-input correspondence (in case of linear input), decimal point position, temperature measurement unit, and offset value are also programmable. Thanks to its universal input, serial interface, and excellent price-to-performance ratio, RT28U-R is a widely applicable device.

Additional information

Захранване

115 VAC, 230 VAC, 90…250 V

Релеен изход

Relay NO

Интерфейс

None, RS485

Протокол

ASCII, ASCII PolyMonitor

Аналогов вход

0…10 V DC linear voltage, 0…20mA DC linear current, 4…20mA DC linear current, RTD Pt100 – 1.385, RTD Pt1000 – 1.385, RTD PTC 1k, RTD PTC 2k, Thermocouple (TC) B, Thermocouple (TC) J, Thermocouple (TC) K, Thermocouple (TC) R, Thermocouple (TC) S, Thermocouple (TC) T, Two-wire external transmitter

Монтаж

DIN rail, In box IP65

Корпус

35x78x91 mm, 70x110x58 mm

Закон за управление

ON/OFF

RT28U-R controller

Current / Voltage / ResistanceHumidityTemperature

Technical Specifications
Input (programmable)
Pt100 (w=1.385); 3-wire-100…850 °C
Pt1000 (w=1.385); 3-wire-100…600 °C
PTC (1k at 25 °C); 3-wire (KT- and KTY-Based)-50…150 °C
PTC (2k at 25 °C); 3-wire (KT- and KTY-Based)-50…150 °C
Thermocouple “T”-40…400 °C
Thermocouple “J”-20…999 °C
Thermocouple “K”-20…999 °C
Thermocouple “S”0…999 °C
Thermocouple “R”0…999 °C
Thermocouple “B”100…999 °C
Linear voltage 0…10 V-199…999, programmable
Linear current 0(4)…20 mA-199…999, programmable
Linear resistive 0…1 kΩ-199…999, programmable
Custom linear (option)(1)-199…999, programmable
Two-wire external transmitter4…20 mA (2)
Manual input offsetprogrammable
Input type selectionprogrammable
Decimal point selectionprogrammable
Temperature measurement unit°C or °F, programmable
Outputs (up to 2 relay outputs)
Relay electromechanical5A/250V w/ NO/NC or NO (3) contact
Solid state relay (SSR) (7)1A/250VAC
MOS gate (7)0.1A/60V, optically isolated
Output for external SSR5…24 V, 30 mA
Control algorithmON/OFF
Set pointwithin input range limits
Alarmsprogrammable
Serial interface (4)RS485, isolated
Accuracy
Measurement error0,3% (5) from span
Temperature drift0.02% from span for 1 °C
Cold junction compensationautomatic, -10…80 °C
RTD line compensationautomatic, up to 2 х 25 Ω
Power supply
Mains supply voltage230 VAC or 115 VAC
SMPS voltage90…250 V
Isolated low voltage12…24 V or 24 VAC
Non-isolated low voltage12…24 V
Consumptionmax. 1.5 VA
Indication and controls
Digital display3 LED indicators
LEDs2 LEDs for output state
Keyboard3 membrane keys
Operating conditions
Ambient temperature-10…65 °C
Ambient humidity0…85 %RH

 

Design and materialsR1R2
Dimensions [mm]70x110x5835x78x91
Mountingon railin socket or on rail
Display digit height [mm]1410
Maximum weight [g]300200
Protection, front/terminalsIP20IP44 / IP20
Case materialplasticplastic
Wiringscrew terminalssocket UNDECAL(6)

(1) Instead of linear current
(2) Provides loop supply voltage – 24 VDC (only w/ isolated power supply).
(3) NO/NC for case ‘R1’; NO for case ‘R2’
(4) Not available for case ‘R2’.
(5) 0.5% for T/Cs “S”, “R”, and “B”
(6) Ordered separately (see ‘Accessories’)
(7) Ask for availability!