Comeco logo

Advantages

  • Dual infrared CO2 sensor
  • Application in air conditioning and HVAC
  • Good accuracy and sensitivity
  • Weak influence of humidity and temperature
  • Option for installation of air ducts
  • Built-in digital display
  • RS232 interface

Description

The PHG transducer measures the concentration of CO2 in the atmospheric air of closed rooms by converting the measured value into a standard current or voltage signal. This model uses a built-in dual infrared sensor providing good accuracy and sensitivity, as well as low dependence on temperature and humidity. The converter can be ordered with a built-in digital display as well as an RS232 interface. PHG there are options for air duct installation or free installation. Available with a straight or angled coupling mounted on the top or bottom of the housing. The field of application of PHG includes the control of air parameters in air conditioning and ventilation, the cultivation of fungi and microorganisms, as well as other applications requiring the measurement of carbon dioxide.

Additional information

Захранване

15…32 VDC

Аналогов вход

Non-dispersive Infrared CO2 cell

Измервателен обхват

0…3000/5000/10000 ppm

Аналогов изход

0…10 V, 0…20 mA, 4…20 mA, Other

Интерфейс

None, RS232

Монтаж

duct mounting, Free

Корпус

80x80x70 mm

PHG carbon dioxide sensor

Carbon Dioxide

Technical Specifications
Input
Input typeNon-dispersive Infrared CO2 cell
Measurement range0…3000/5000/10000 ppm
Accuracy
Measurement error (1)± 2 ppm (0…3000 ppm) at 10…50 ⁰С
Temperature dependence10 ppm for 1 °C
Warm-up timemax. 90 s (at 25 °C)
Response time (0…80%)max. 30 s (w/o sintered filter)
Output
Output signal0(4)…20 mA0…10 V
Output update2 s2 s
Minimum output load1 MΩ
Maximum output load350 Ω at 20 mA
Over-scale limitmax. 35 ± 2 mA17 ± 2 V
Interface
Interface typeRS232, 9600 bps
FunctionCO2 data transmission
ProtocolASCII, free
Power supply
Supply voltage15…32 VDC
Admissible variations1 Vp-p at 50 Hz
Consumptionmax. 90 mA (150 mA w/ indicator)
Local indicator
Digital display4 LED indicators, 14 mm
Display resolution1 ppm
Display refresh1 s
Accuracy0.2% from span
Temperature drift0.01% from span for 1 °C
Operating conditions
Operating temperature0…50 °C
Operating humidity0…85 %RH, non-condensing
Storage temperature-10…60 °C

 

Design and materials
Case materialABS/PC plastic
Inlet materialPOM plastic
Housing dimensions (no connector)80x80x70 mm
Wiring4-pin 812 connector (2)
Sensor protectionplastic cap with polyester filter
Sintered filter (option)stainless steel, 75 μm
Protection classIP65 (excluding gas inlet)
Mountingfree (3)duct
Process connectionnonemovable flange (4)
Gas inlet length30 mm130 mm
Weightmax. 250 gmax. 350 g

(1) Including nonlinearity error
(2) Straight or angles female part included
(3) Radial and axial mounting accessories can be ordered separately (see ‘Accessories’)
(4) Small POM flange DN16.5.