Comeco logo

Advantages

  • 11-pin relay socket for fast rail mounting
  • 1500 VAC input / output / supply isolation
  • Universal programmable input
  • Programmable output
  • Built-in programmable digital filter
  • Built-in programmable digital filter
  • Manual output control
  • Serial interface for programming

Description

TRZ is a reliable temperature transmitter designed for precise measurement and conversion of temperature signals into a standard analog output (4–20 mA or 0–10 V). Compatible with various temperature sensors, including Pt100 and thermocouples, TRZ provides stable and accurate operation in industrial conditions. Its compact design allows easy mounting in a thermoprobe head or on a DIN rail, offering flexibility in integration into various automation and control systems.

The transmitter allows the user to:

  • select the sensor type and input signal (RTD, TD, mA, mV, V, R);
  • select and set the input range;
  • select the type of output signal (0(4)…20 mA or 0…10 V);
  • control the output manually;
  • enter zero correction and calibrate the output;
  • select the input / output correspondence (direct or inverse);
  • select the unit of measurement and the position of the decimal point;
  • select the state of the output signal in case of a sensor defect;
  • set the digital filters.
  • TRZ is easy to program using the specialized “TraCon” software. Thanks to its convenient box with a connector, the transmitter can be mounted both in standard relay sockets and on a DIN rail.

TRZ transmitter applications:

  • Industrial automation and process control
  • HVAC (heating, ventilation and air conditioning) systems
  • Power and district heating installations
  • Food and beverage and pharmaceutical industries
  • Temperature monitoring in machines and equipment

Additional information

Монтаж

DIN rail, In socket

Корпус

35x78x91 mm

Захранване

115 VAC, 230 VAC

Интерфейс

RS232

Аналогов вход

0…10 V DC linear voltage, 0…100 mV DC linear voltage, 0…20mA DC linear current, 4…20mA DC linear current, Custom linear signal, Other, RTD Pt100 – 1.385, RTD Pt1000 – 1.385, RTD PTC 1k, RTD PTC 2k, Thermocouple (TC) B, Thermocouple (TC) J, Thermocouple (TC) K, Thermocouple (TC) R, Thermocouple (TC) S, Thermocouple (TC) T

Аналогов изход

0…10 V, 0…20 mA, 10…0 V, 20…0 mA, 20…4 mA, 4…20 mA

TRZ – Precision Temperature Transmitter with Analog Output

Temperature

Technical Specifications
Input (programmable)
Pt100 (w=1.385); 3-wire (DIN IEC 60751)min. -200…max. 850 °C
Pt1000 (w=1.385); 3-wire (DIN IEC 60751)min. -100…max. 600 °C
PTC (1k at 25 °C); 3-wire (KT and KTY-based) min. -50…max. 150 °C
PTC (2k at 25 °C); 3-wire (KT and KTY-based) min. -50…max. 150 °C
RTD minimum range width50 °C
Thermocouple “T” (DIN IEC 60584)min. -40…max. 400 °C
Thermocouple “J” (DIN IEC 60584)min. -20…max. 1000 °C
Thermocouple “K” (DIN IEC 60584)min. -20…max. 1300 °C
Thermocouple “S” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “R” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “B” (DIN IEC 60584)min. 200…max. 1800 °C
T/C minimum range width 100 °C
Linear current 0(4)…20 mA
Linear voltage0…100 mV, 0…10 V
Linear resistive 0…1 kΩ
Custom linear (option) on request (1)
Offset adjustmentwithin range limits
Digital low-pass filterprogrammable
Digital peak filterprogrammable
Input / output isolation 1500 VAC for 1 min
Input monitoring
(programmable)
Sensor failure reaction0 mA or > 20.2 mA, programmable
Output (programmable)
Current 0(4)…20 mA or 20…0(4) mA
– loadmax. 600 Ω at 20 mA
Voltage 0…10 V or 10…0 V
– loadmin. 2 kΩ at 10 V
Linearly proportional tomeasured value
Resolution4 μA / 2,5 mV
Output calibrationthrough interface
Manual output control 0…100%, programmable
Excitation voltage18…28 VDC, max. 30 mA
Accuracy
Measurement error 0.3% from span
Non-linearity within measurement error
Temperature drift0.01% from span for 1 °C
Cold junction compensationautomatic software, ± 0.5 °C
Power supply
Mains supply voltage 230 VAC or 115 VAC ± 10%
Isolated low voltage12…24 V or 24 VAC
Consumptionmax. 1.5 VA
Indication
‘Power’ LED for power supply ON
‘Load’ LEDfor voltage output overload
‘Alarm’ LEDfor broken current output loop
Interface
Interface typeRS232-based
Physical connectionrequiring special cable (2)
Configuration softwareTraCon”, free
Operating conditions
Ambient temperature -20…70 °C
Ambient humidity 0…95 %RH, non-condensing
Design and materials
Case materialplastic
Mounting in socket or on 35 mm DIN rail
Wiringsocket UNDECAL (2)
Interface connector3-pin
Interface cable type(2)K2 (RS232) or K12U (USB)
Dimensions 35x78x91 mm
Weight 180 g
Protection classIP20

(1) Instead of linear current or voltage 0…10 V