Comeco logo

Advantages

  • 11-pin relay socket for fast rail mounting
  • 1500 VAC input / output / supply isolation
  • Universal programmable input
  • Programmable output
  • Built-in programmable digital filter
  • Built-in programmable digital filter
  • Manual output control
  • Serial interface for programming

Description

The intelligent isolated transmitter TRZ can be a proper solution when different signal conversions are needed. This transmitter allows the user to:

  • select sensor and input signal type (RTD, T/C, mA, mV, V, R);
  • select and adjust input range;
  • select output type (0(4)…20 mA or 0…10 V);
  • control the output manually;
  • perform offset correction and device calibration;
  • specify the input-to-output correspondence (direct or reverse);
  • select decimal point position and measurement unit;
  • select output reaction at sensor failure;
  • adjust the digital filter.

The TRZ transmitter is easy to program via the specialized configuration software “TraCon”. Thanks to its convenient 11-pin connector case, TRZ can be easily fit in a standard UNDECAL socket and mounted on DIN rail.

Additional information

Монтаж

DIN rail, In socket

Корпус

35x78x91 mm

Захранване

115 VAC, 230 VAC

Интерфейс

RS232

Аналогов вход

0…10 V DC linear voltage, 0…100 mV DC linear voltage, 0…20mA DC linear current, 4…20mA DC linear current, Custom linear signal, Other, RTD Pt100 – 1.385, RTD Pt1000 – 1.385, RTD PTC 1k, RTD PTC 2k, Thermocouple (TC) B, Thermocouple (TC) J, Thermocouple (TC) K, Thermocouple (TC) R, Thermocouple (TC) S, Thermocouple (TC) T

Аналогов изход

0…10 V, 0…20 mA, 10…0 V, 20…0 mA, 20…4 mA, 4…20 mA

TRZ transmitter

Temperature

Technical Specifications
Input (programmable)
Pt100 (w=1.385); 3-wire (DIN IEC 60751)min. -200…max. 850 °C
Pt1000 (w=1.385); 3-wire (DIN IEC 60751)min. -100…max. 600 °C
PTC (1k at 25 °C); 3-wire (KT and KTY-based) min. -50…max. 150 °C
PTC (2k at 25 °C); 3-wire (KT and KTY-based) min. -50…max. 150 °C
RTD minimum range width50 °C
Thermocouple “T” (DIN IEC 60584)min. -40…max. 400 °C
Thermocouple “J” (DIN IEC 60584)min. -20…max. 1000 °C
Thermocouple “K” (DIN IEC 60584)min. -20…max. 1300 °C
Thermocouple “S” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “R” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “B” (DIN IEC 60584)min. 200…max. 1800 °C
T/C minimum range width 100 °C
Linear current 0(4)…20 mA
Linear voltage0…100 mV, 0…10 V
Linear resistive 0…1 kΩ
Custom linear (option) on request (1)
Offset adjustmentwithin range limits
Digital low-pass filterprogrammable
Digital peak filterprogrammable
Input / output isolation 1500 VAC for 1 min
Input monitoring
(programmable)
Sensor failure reaction0 mA or > 20.2 mA, programmable
Output (programmable)
Current 0(4)…20 mA or 20…0(4) mA
– loadmax. 600 Ω at 20 mA
Voltage 0…10 V or 10…0 V
– loadmin. 2 kΩ at 10 V
Linearly proportional tomeasured value
Resolution4 μA / 2,5 mV
Output calibrationthrough interface
Manual output control 0…100%, programmable
Excitation voltage18…28 VDC, max. 30 mA
Accuracy
Measurement error 0.3% from span
Non-linearity within measurement error
Temperature drift0.01% from span for 1 °C
Cold junction compensationautomatic software, ± 0.5 °C
Power supply
Mains supply voltage 230 VAC or 115 VAC ± 10%
Isolated low voltage12…24 V or 24 VAC
Consumptionmax. 1.5 VA
Indication
‘Power’ LED for power supply ON
‘Load’ LEDfor voltage output overload
‘Alarm’ LEDfor broken current output loop
Interface
Interface typeRS232-based
Physical connectionrequiring special cable (2)
Configuration softwareTraCon”, free
Operating conditions
Ambient temperature -20…70 °C
Ambient humidity 0…95 %RH, non-condensing
Design and materials
Case materialplastic
Mounting in socket or on 35 mm DIN rail
Wiringsocket UNDECAL (2)
Interface connector3-pin
Interface cable type(2)K2 (RS232) or K12U (USB)
Dimensions 35x78x91 mm
Weight 180 g
Protection classIP20

(1) Instead of linear current or voltage 0…10 V

(2) Ordered separately (see ‘Accessories)