Comeco logo

Advantages

  • Transmitter with universal programmable input
  • User-selectable 4 RTD types and 6 thermocouples
  • Accepts linear current, voltage, and resistive signals
  • Programmable input and output range
  • Built-in programmable digital filter
  • Manual output control
  • Serial interface for programming
  • IP65 box and Ex housing available

Description

TRB is an economical yet reliable temperature transmitter with a fixed analog output signal (4…20 mA or 0…10 V). Available with Pt100 or thermocouple input, in a compact housing for head mounting or DIN rail mounting. An excellent choice for temperature control automation in industrial processes and HVAC systems. Configuration is done at the factory, with no need for user settings.

The transmitter allows the user to:

  • select the sensor type and input signal;
  • select and set the input range;
  • enter zero correction and calibrate the output;
  • define the input limits and output type (4…20 mA / 20…4 mA);
  • select the unit of measurement and the position of the decimal point;
  • select the output signal state in case of sensor failure;
  • set the digital filters.

TRB is easy to program using the specialized software “TraCon”. Thanks to its wide capabilities and low cost, TRB is very useful when temperature conversion is required before subsequent measurement or control.

TRB transmitter applications:

  • Industrial automation and production lines
  • HVAC systems
  • Energy and district heating installations
  • Food and beverage and pharmaceutical industries
  • Temperature monitoring in machines and facilities

Additional information

Монтаж

DIN rail, In box IP65, In head, In Ex housing

Корпус

18x90x58 mm, 80x80x60 mm, ø44×23 mm

Аналогов вход

RTD Pt100 – 1.385, RTD Pt1000 – 1.385, RTD PTC 1k, RTD PTC 2k, Thermocouple (TC) B, Thermocouple (TC) J, Thermocouple (TC) K, Thermocouple (TC) R, Thermocouple (TC) S, Thermocouple (TC) T

Захранване

8…32 VDC

Аналогов изход

20…4 mA, 4…20 mA

Интерфейс

RS232

TRB – Precision Temperature Transmitter with Analog Output

Current / Voltage / ResistanceTemperature

Technical Specifications
Input (programmable)
Pt100 (w=1.385); 3-wire (DIN IEC 60751)min. -100…max. 850 °C
Pt1000 (w=1.385); 3-wire (DIN IEC 60751)min. -100…max. 600 °C
PTC (1k at 25 °C); 3-wire (KT и KTY-базирани)min. -50…max. 150 °C
PTC (2k at 25 °C); 3-wire (KT и KTY-базирани)min. -50…max. 150 °C
RTD minimum range width 50 °C
Thermocouple “T” (DIN IEC 60584)min. -40…max. 400 °C
Thermocouple “J” (DIN IEC 60584)min. -20…max. 1000 °C
Thermocouple “K” (DIN IEC 60584)min. -20…max. 1300 °C
Thermocouple “S” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “R” (DIN IEC 60584)min. 0…max. 1700 °C
Thermocouple “B” (DIN IEC 60584)min. 200…max. 1800 °C
T/C minimum range width 100 °C
Linear current0(4)…20 mA
Linear voltage
0…100 mV or 0…10 V (1)
Linear resistive0…1 kΩ
Custom linear (option)on request (2)
Offset adjustmentwithin range limits
Digital low-pass filterprogrammable
Digital peak filterprogrammable
Input monitoring (programmable)
Sensor failure reaction 20,2 mA, programmable
Output (programmable)
Signal type4…20 mA or 20…4 mA
Linearly proportional tomeasured value
Resolution4 µA
Output calibrationthrough interface
Manual output control0…100%, programmable
Accuracy
Measurement error 0.3% from span
Non-linearitywithin measurement error
Temperature drift 0.01% from span for 1 °C
Cold junction compensation automatic software, ± 0.5 °C
Power supply
Supply voltage8…32 VDC ± 10%
Maximum line load750 & at 24V/20mA
Interface
Interface typeRS232 -based
Physical connectionrequiring special cable (3)
Configuration softwareTraCon”, free
Operating conditions
Ambient temperature-20…70 °C
Ambient humidity0…95 %RH, non-condensing
Design and materials
Case materialplastic
Mounting screw terminals
Mounting in head (4,5,6)on railin box (5)
Interface connector 4-pin 3-pin 4-pin
Interface cable type (3)K1, K1U, K11UK2, K2U, K12UK1, K1U, K11U
Dimensions [mm]ø44×2318x90x5880x80x60
Weight40 g60 g180 g
Protection classIP20IP20IP65

(1) Ask for availability!

(2) Instead of linear current

(3) Ordered separately

(4) Head type “B” or any other with 33 mm distance between centers of the female threaded openings

(5) May be mounted on rail by a special snap-on accessory, which is ordered separately (see ‘Accessories’).