Comeco logo

Advantages

  • Installation without the need to remove the floats
  • Up to 5 floats
  • Up to 5 switching points
  • 135 °C maximum liquid temperature
  • Various float and detachable connector types
  • Vertical adjustment option
  • Temperature measurement option

Description

The operation of COMECO’s level probe LCSFK is based on the switching of reed switches by magnetic floats, moving alongside a protective tube. Large variety of versions based on different floats is available. The floats can be made of stainless steel or plastic; floats with different dimensions and specific gravity are available for liquid density down to 0.45 g/cm3, temperature up to 135 °C, and pressure up to 50 bar. Maximum 5 switching points can be mounted in a single probe, and the reed switches are capable of switching directly different loads. The wiring is attained with convenient detachable DIN connector. Various process connections are available as well as an optional vertical adjustment.

Additional information

Материал на поплавък

Plastic, Stainless steel

Функция на контакта

NC (opens at float down), NC (opens at float up), NO (closes at float down), NO (closes at float up)

Комутационна способност

120 V / 0.5 A / 10 W, 230 V / 0.5 A / 10 W, 230 V / 1 A / 30 W, 230 V / 2 A / 50 W

Присъединяванe

Flange, G1'', G1½", G1¼", G2", G3", G3/4", M27x2, M33x2, NPT 1", NPT 1½", NPT 1¼", NPT 2", NPT 3", NPT 3/4", Other

Вграден температурен сензор/термостат

None, Pt100, Pt1000, Thermostat

LCSFK multi-point float level switch with connector

Level

Technical Specifications
Model LCSFK w/ SS floats
Specifications
Float typeS0 / S1 / S7 / S10 S2 S3/S4S11S5 S6 S8 / S9 S20
Liquid density [g/cm3] > 0.80 (1)> 0.70 > 0.65/> 0.55 > 0.45> 0.55 > 0.50> 0.50 /> 0.45> 0.75
Number of floats1…31…31…41…41…51…51…51…3
Ext. tube diameter (‘d’)8 mm10 mm14 mm14 mm16/18 mm16/18 mm18/25 mm8 mm
Contact type (2)NO,NCNO/NCNO,NCNO/NCNO,NCNO/NCNO,NCNO/NCNO,NCNO/NCNO,NCNO/NCNO,NCNO/NCNO,NCNO/NC
Maximum wire leads46666664
Max. common-lead contacts35252525252523
Max. separated contacts2132323232323221
Contact ratings‘1’: max. 120 VAC, max. 0.5 A, max. 10 W; ‘2’: max. 230 VAC, max. 0.5 A, max. 10 W; ‘3’: max. 230 VAC, max. 2 A, max. 50 W; ‘4’: max. 230 VAC, max. 1 A, max. 30 W
Temp. sensor / thermostatbuilt-in RTD (Pt100, Pt1000) or bimetallic thermostat (see specifications below) (option)
Probe length (‘L0’)100…1000 mm100…2000mm200…3000mm80…4000mm300…4000mm300…5000mm300…5000mm100…1000mm
End-to-float distance (‘A’)min.22/25/25/29mmmin. 34 mmmin. 40/39 mmmin. 37 mmmin. 50 mmmin. 70 mmmin. 65/90 mmmin. 36 mm
Float running distance (‘B’)min.25/30/30/34mmmin. 40 mmmin. 57/54 mmmin. 60 mmmin. 75 mmmin. 110 mmmin.102/152mmmin. 42 mm
Float-to-float distance (‘C’)min.45/50/50/58mmmin. 68 mmmin. 82/78 mmmin. 75 mmmin. 100 mmmin. 136 mmmin.126/157mmmin. 72 mm
Process temperature-20…135 °C
Ambient temperature-20…75 °C
Max. process pressure8 / 10 / 30 / 50 bar30 bar12/30 bar15 bar30 bar10 bar30 bar30 bar
Process connectionmin. 1″ (M33)min. 1½”min. 2″min. 2″min. 3″ or flangemin. 3″ or flangeflangemin. ¾” (M27)
Wiringup to 4 terminals (contact leads): 4-pin (3+PE) detachable connector DIN 43650 or detachable circular connector M12;
up to 6 terminals (contact leads): 7-pin (6+PE) detachable connector DIN 43651
Wetted partsstainless steel
ProtectionIP65
Built-in temperature sensor / thermostat (option)
RTD sensorthermostat
TypePt100 or Pt1000NC (under set point)
Ratings2-wiremax. 250 VAC / 1.6 A
Set point40…130 °C (step 5 °C)
Accuracyclass ‘B’± 5 °C
Terminals occupied22 or 1 (+ common)
Probe extension≈ 30 mm
Model LCSFK w/ plastic floats
Specifications
Float typeP0N1P1P10P2P3P4
Float materialPPNBRPPPPPPPPPVDF
Liquid density [g/cm3] > 0,73> 0,60> 0,60> 0,72> 0,60> 0.50> 0,70
Number of floats11…31…31…31…41…51…5
Ext. tube diameter (‘d’)6 mm8 mm8 mm10 mm12 mm16 mm16 mm
Contact type (2)NO, NCNO, NCNO/NCNO, NCNO/NCNO, NCNO/NCNO, NCNO/NCNO, NCNO/NCNO, NCNO/NC
Maximum wire leads2446666
Max. common-lead contacts3352525252
Max. separated contacts1212132323232
Contact ratings‘1’: max. 120 VAC, max. 0.5 A, max. 10 W; ‘2’: max. 230 VAC, max. 0.5 A, max. 10 W; ‘3’: max. 230 VAC, max. 2 A, max. 50 W; ‘4’: max. 230 VAC, max. 1 A, max. 30 W
Temp. sensor / thermostatbuilt-in RTD (Pt100, Pt1000) or bimetallic thermostat (see specifications below) (option)
Probe length (‘L0’)50…500 mm100…1000 mm100…1000 mm50…2000 mm100…2000 mm200…4000 mm200…4000 mm
End-to-float distance (‘A’)min. 18 mmmin. 23 mmmin. 21 mmmin. 15 mmmin. 37 mmmin. 47 mmmin. 47 mm
Float running distance (‘B’)min. 20 mmmin. 27 mmmin. 24 mmmin. 17 mmmin. 52 mmmin. 62 mmmin. 62 mm
Float-to-float distance (‘C’)min. 45 mmmin. 42 mmmin. 30 mmmin. 76 mmmin. 86 mmmin. 86 mm
Process temperature-20…80 °C-20…100 °C-20…80 °C-20…80 °C-20…80 °C-20…80 °C-20…80 °C
Ambient temperature-20…75 °C
Max. process pressure5 bar0 bar5 bar5 bar3 bar3 bar2 bar
Process connectionmin. ¾” (M24)min. ½” (M20)min. 1″ (M33)min. 1″ (M33)min. 1″ (M33)min. 1 ¼”min. 1 ¼”
Wiringup to 4 terminals (contact leads): 4-pin (3+PE) detachable connector DIN 43650 or detachable circular connector M12;
up to 6 terminals (contact leads): 7-pin (6+PE) detachable connector DIN 43651
Wetted partsstainless steel (except floats)
ProtectionIP65
Built-in temperature sensor / thermostat (option)
RTD sensorthermostat
TypePt100 or Pt1000NC (under set point)
Ratings2-wiremax. 250 VAC / 1.6 A
Set point40…130 °C (step 5 °C)
Accuracyclass ‘B’± 5 °C
Terminals occupied22 or 1 (+ common)
Probe extension≈ 30 mm

(1) > 0.70 g/cm3 for float type ‘S1’
(2) Different contact types can be ordered.